Flue gas stack: Difference between revisions

From Citizendium
Jump to navigation Jump to search
imported>Milton Beychok
(Revised a link)
imported>Caesar Schinas
m (Bot: Adding)
Line 109: Line 109:
==References==
==References==
{{reflist}}
{{reflist}}


[[Category:CZ Live]]
[[Category:CZ Live]]

Revision as of 07:32, 6 June 2009

This article is developed but not approved.
Main Article
Discussion
Related Articles  [?]
Bibliography  [?]
External Links  [?]
Citable Version  [?]
 
This editable, developed Main Article is subject to a disclaimer.
(PD) Photo: U.S. EPA
Flue gas stacks in the Navajo Generating Station in Arizona

A flue gas stack is a vertical pipe, channel or similar s structure through which combustion product gases called "flue gases" are exhausted to the outside air. Flue gas stacks are sometimes referred to as a "smokestacks".

Flue gases are produced when coal, fuel oil, natural gas, wood or any other fuel is combusted in an industrial furnace or boiler, a steam-generator in a fossil fuel power plant or other large combustion device. Flue gas is usually composed of carbon dioxide (CO2) and water vapor as well as nitrogen and excess oxygen remaining from the intake combustion air. It also contains a small percentage of pollutants such as particulate matter, carbon monoxide, nitrogen oxides and sulfur oxides. The flue gas stacks are often quite tall, up to 400 meters (1300 feet) or more, so as to disperse the exhaust pollutants over a greater area and thereby reduce the ground-level concentration of the pollutants to comply with governmental air pollution control regulations.

When the flue gases are exhausted from stoves, ovens, fireplaces, or other small sources within residential abodes, restaurants, hotels, or other public buildings and small commercial enterprises, their flue gas stacks are referred to as "chimneys".

History

The first industrial chimneys were built in the mid-17th century when it was first understood how they could improve the combustion of a furnace by increasing the draft (draught) of air into the combustion zone.[1] As such, they played an important part in the development of reverberatory furnaces and a coal-based metallurgical industry, one of the key sectors of the early Industrial Revolution. Most 18th century industrial chimneys (now commonly referred to as flue gas stacks) were built into the walls of the furnace much like a domestic chimney. The first free-standing industrial chimneys were probably those erected at the end of the long condensing chimneys associated with smelting lead.

The powerful association between industrial chimneys and the characteristic smoke-filled landscapes of the industrial revolution was due the universal application of the steam engine for most manufacturing processes. The chimney is part of a steam-generating boiler, and its evolution is closely linked to increases in the power of the steam engine. The chimneys of Thomas Newcomen’s steam engine were incorporated into the walls of the engine house. The taller, free-standing industrial chimneys that appeared in the early 19th century were related to the changes in boiler design associated with James Watt’s "double-powered" engines, and they continued to grow in stature throughout the Victorian period. Decorative embellishments are a feature of many industrial chimneys from the 1860s.

The invention of fan-assisted draft (draught) in the early 20th century removed the industrial chimney's original function, that of drawing air into the steam-generating boilers or other furnaces. With the replacement of the steam engine as a prime mover, first by diesel engines and then by electric motors, the early industrial chimneys began to disappear from the industrial landscape. Building materials changed from stone and brick to steel and later reinforced concrete, and the height of the industrial chimney was determined by the need to disperse combustion flue gases to comply with governmental air pollution control regulations.

(PD) Image: Milton Beychok
Outside and inside pressure difference causes draft in a flue gas stack. Light gray arrows indicate flue gas flow.

Flue gas stack draft (or draught)

The combustion flue gases inside the flue gas stacks are much hotter than the ambient outside air and therefore less dense than the ambient air. That causes the bottom of the vertical column of hot flue gas to have a lower pressure than the pressure at the bottom of a corresponding column of outside air. That higher pressure outside the chimney is the driving force that moves the required combustion air into the combustion zone and also moves the flue gas up and out of the chimney. That movement or flow of combustion air and flue gas is called "natural draft (or draught)", "natural ventilation", "chimney effect", or "stack effect". The taller the stack, the more draft (or draught) is created.

The equation below provides an approximation of the pressure difference, ΔP, (between the bottom and the top of the flue gas stack) that is created by the draft:[2][3]

where:

ΔP = available pressure difference, in Pa
C = 0.0342
a = absolute atmospheric pressure, in Pa
h = height of the flue gas stack, in m
To = absolute outside air temperature, in K
Ti = absolute average temperature of the flue gas inside the stack, in K

The above equation is an approximation because it assumes that the molecular weight of the flue gas and the outside air are equal and that the pressure drop through the flue gas stack is quite small. Both assumptions are fairly good but not exactly accurate.

The flue gas flow rate induced by the draft

As a "first guess" approximation, the following equation can be used to estimate the flue gas flow rate induced by the draft of a flue gas stack. The equation assumes that the molecular weight of the flue gas and the outside air are equal and that the frictional resistance and heat losses are negligible:[4]

where:  
Q = flue gas flow rate, in m³/s
A = cross-sectional area of chimney, in m² (assuming it has a constant cross-section)
C = discharge coefficient (usually taken to be from 0.65 to 0.70)
g = gravitational acceleration at sea level, 9.807 m/s²
H = height of chimney, in m
Ti = absolute average temperature of the flue gas in the stack, in K
To = absolute outside air temperature, in K

Designing chimneys and stacks to provide the correct amount of natural draft involves a great many factors such as:

  • The height and diameter of the stack.
  • The desired amount of excess combustion air needed to assure complete combustion.
  • The temperature of the flue gases leaving the combustion zone.
  • The composition of the combustion flue gas, which determines the flue gas density.
  • The frictional resistance to the flow of the flue gases through the chimney or stack, which will vary with the materials used to construct the chimney or stack.
  • The heat loss from the flue gases as they flow through the chimney or stack.
  • The local atmospheric pressure of the ambient air, which is determined by the local elevation above sea level.

The calculation of many of the above design factors requires trial-and-error reiterative methods.

Governmental agencies in most countries have specific codes which govern how such design calculations must be performed. Many non-governmental organizations also have codes governing the design of chimneys and stacks (notably, the ASME codes).

Other items of interest

It should be noted that not all fuel-burning industrial equipment rely upon natural draft. Many such equipment items use large fans or blowers to accomplish the same objectives, namely: the flow of combustion air into the combustion chamber and the flow of the hot flue gas out of the chimney or stack.

A great many power plants are equipped with facilities for the removal of sulfur dioxide via flue gas desulfurization as well as removal of nitrogen oxides (NOx) via selective catalytic reduction, exhaust gas recirculation, thermal deNOx, or low NOx burners.

In the United States and a number of other countries, atmospheric dispersion modeling[5] studies are required to determine the flue gas stack height needed to comply with the local air pollution regulations. The United States also limits the maximum height of a flue gas stack to what is known as the "Good Engineering Practice (GEP)" stack height.[6][7] In the case of existing flue gas stacks that exceed the GEP stack height, any air pollution dispersion modeling studies for such stacks must use the GEP stack height rather than the actual stack height.

References

  1. Douet, James (1988). Going up in Smoke:The History of the Industrial Chimney, Victorian Society, London, England. Victorian Society Casework Reports
  2. Natural Ventilation Lecture 2
  3. Perry, R.H. and Green, Don W. (1984). Perry's Chemical Engineers' Handbook, 6th Edition (page 9-72). McGraw-Hill Book Company. ISBN 0-07-049479-7. 
  4. Natural Ventilation Lecture 3
  5. Beychok, Milton R. (2005). Fundamentals Of Stack Gas Dispersion, 4th Edition. author-published. ISBN 0-9644588-0-2.  www.air-dispersion.com
  6. Guideline for Determination of Good Engineering Practice Stack Height (Technical Support Document for the Stack Height Regulations), Revised (1985), EPA Publication No. EPA–450/4–80–023R, U.S. Environmental Protection Agency (NTIS No. PB 85–225241)
  7. Lawson, Jr., R.E. and W.H. Snyder (1983). Determination of Good Engineering Practice Stack Height: A Demonstration Study for a Power Plant, EPA Publication No. EPA–600/3–83–024. U.S. Environmental Protection Agency (NTIS No. PB 83–207407)